Gold Member Since 2006
Audited Supplier
Andeli Group Co., Ltd.

Electrical Products, Relay & Contactor, Lc1-D32 Ac Contactor manufacturer / supplier in China, offering Cjx7 AC Contactor Magnetic Contactor Price (CJX7-75), 125AMP MCCB Moulded Case Circuit Breaker (AM1), Kilo Watt-hour Meter (DD28 DD862 DT862 DT8) and so on.

(/ )

Supplier Homepage Product Relay / Contactor / Starter/ Frequency Inverter Cjx7 AC Contactor Magnetic Contactor Price (CJX7-75)

Cjx7 AC Contactor Magnetic Contactor Price (CJX7-75)

FOB Price: Get Latest Price
Min. Order: 1 Piece
Production Capacity: 5000 Pieces/Day
Transport Package: Carton
Payment Terms: L/C, T/T, D/P, Paypal, Western Union

Request a custom order and have something just for you!

Send Customized Request
Basic Info
  • Model NO.: CJX7-75
  • Number of Pole: 4
  • Type: Ac Contactors
  • Size: Miniature
  • Trademark: ANDELI
  • Origin: China
  • Electricity Type: AC
  • Phase: 1, 3
  • Working Voltage: up to 660V
  • Usage: Industrial
  • Specification: ISO9000; CE; CB; CCC
Product Description
Why choose us?
1.20 years - Andeli Group Co., Ltd is founded in 1993.
2.12 share holding companies - Andeli have owns 12 share holding companies in Shanghai, Hunan, Zhejiang, UAE.
3.300 cooperating companies - We have over 300 cooperating companies.
4.3000 workers - We have over 3000 workers.
5. USD150, 000, 000 - The total assets is USD150, 000, 000.
6.235, 000 square meters - The area of Andeli is 235, 000 square meters.
7. Certification - We have passed ISO9001: 2000 Quality Management System and CCC, ROHS, CE, CB, SIMKO, KEMA...
1. Application

CJX7-9~300 AC contactor(hereafter refer to as contactor)is mainly used in power system with AC 50Hz(or 60Hz), therated working voltage up to 660V, under the application category of AC-3, when the rated working voltage 380V, the rated operating current to 300A electrical, for the long-distance range making and breaking the electric circuit, and combines the electorm agnetism starter with the suitable thermal overload relay or the electronic protector to protect against the possible overload electric circuit during operation(running).

2. Technical parameter

2.1 The allowable application category of main circuit and the auxiliary circuit of the contactor and it's code see Table 1

Table 1 application category of main circuit and the auxiliary circuit of the contactor and it's code
Type Frame code Rated insulation Convensional free air heat AC-3 rated operating current Ie A     AC-3 control the max. power KW of generator    
    voltage Ui V current Ith 220V 380V 660V 220V 380V 660V
CJX7-9 16 1000 26 9 9 7 2.2 4 5.5
CJX7-12 28 12 12 9 3 5.5 6.5
CJX7-16 30 17 17 10 4 7.5 9
CJX7-26 26 45 26 26 17 6.5 11 15
CJX7-30 40 65 32 32 21 9 15 18.5
CJX7-40 65 37 37 25 11 8.5 22
CJX7-50 75 100 50 50 35 15 22 30
CJX7-63 125 65 65 43 18.5 30 37
CJX7-75 125 75 75 46 22 37 40
CJX7-95 110 145 96 96 65 25 45 55
CJX7-110 160 110 110 82 30 55 75
CJX7-145 185 250 145 145 120 40 75 100
CJX7-185 275 185 185 170 50 90 120
CJX7-210 300 350 210 210 210 60 110 150
CJX7-260 400 260 260 260 78 140 190
CJX7-300 450 300 300 280 88 160 220
 